Climate control enclosure can
be operated for many years, however such factors as condensate, humidity,
temperature drop significantly reduce the service life and stable operation of
equipment. Specialists will agree that optimal temperature in an enclosure is a
guarantee of safe, long-term and comfortable operation.
Cooling in climate control
enclosures is divided into passive and active one. Passive cooling provides for
such arrangement of internal space, which ensures free circulation of air in
unoccupied space of the enclosure, which air comes into the enclosure and exits
it through holes in perforated doors and walls. However not always the passive
cooling is sufficient. In most cases in order to maintain operating
micro-climate of the equipment the active cooling shall be arranged.
For arrangement of active
cooling the following is used:
forced ventilation;
Cooling by means of fans is
efficient when temperature of ambient environment is 10 degrees lower than the
temperature recommended for equipment inside of the enclosure. With the purpose
of efficient air circulation the fan units will be installed on the bottom and
on the roof of enclosure. Bottom fans are designed to blow cool air masses into
the enclosure body whereas coolers on the roof discharge heated air outside of
the structure. One more option of fan units installation is fixing them on side
walls of enclosure. Longitudinal cooling of equipment will be effected this
way, which also ensures effective protection from overheating.
Air flow parameter can be
calculated using the formula:
V = 3.1 * Qv / ΔT,
Where, 3,1 is air constant
value,
Qv – heat emission from
components in control enclosure,
ΔT – difference of
temperatures between maximum allowable air temperature inside of enclosure and
ambient temperature.
If device requires protective
way of cooling usually two basic options are distinguished: air conditioner or
heat exchanger.
Air conditioners are applied
in the following cases:
if temperature inside of the
body is not higher than ambient temperature;
if it is necessary to reduce
humidity;
if electronic system generates
medium or large amount of heat.
Cooling capacity of air
conditioner shall be not lower than the heat load generated by electrical
equipment.
Total heat load is generated
by two sources:
a) electronic components (so
called internal heat load);
b) heat of ambient environment
(i.e. heat exchange can significantly increase overall heat load on the system
especially under high air temperature or in case the body is subject to direct
impact of sun rays).
In order to calculate
productivity of air conditioner the following formula shall be used:
Pк = Qv - Pr,
where Pк – air conditioner
productivity;
Qv – heat emission from
components in control enclosure;
Pr [Watt] – heat output
through enclosure body walls (without consideration of insulation ratio).
Pr = k × A × ΔT,
k – heat output ratio;
А- wall surface area, which is
in contact with the ambient environment, m2;
ΔT – difference between
maximum allowable air temperature inside of enclosure and ambient temperature
Air conditioner capacity is
determined as per efficiency chart, which you can see on the picture. Air
conditioner efficiency shall be higher than the level of heat loss from the
components approximately by 10%.
Efficiency curve for
determination of air conditioner capacity
Heat output ratio is radiation
power per 1 m2 of surface area. It is a constant value and depends
on material:
|
Material |
Heat output
ratio, k |
|
Steel sheet |
5,5 W/m2 |
|
Stainless steel |
5,5 W/m2 |
|
Aluminum |
12,0 W/m2 |
|
Plastic |
3,5 W/m2 |
Surface area is measured in
accordance with VDE 0660 part 500 specification. Calculation depends on
location of enclosure:
|
One enclosure,
free standing A = 1,8H · (W + D) + 1,4 · W · D |
|
One enclosure,
wall mounted A = 1,4 · W · (H + D) + 1,8 · D · H |
|
Utmost enclosure,
free standing in a row A = 1,4 · D ·
(H + W) + 1,8 · W · H |
|
Utmost enclosure,
wall mounted A = 1,4 · H · (W + D) + 1,4 · W · D |
|
Not utmost
enclosure, free standing in a row A = 1,8 · W · H + 1,4 · W · D + D · H |
|
Not utmost
enclosure, to be mounted onto wall А = 1,4 · W · (H + D) + D · H |
|
Not utmost
enclosure, to be mounted into wall, under a canopy A = 1,4 · W · H +
0,7 · W · D + D · H |
Where W is enclosure
width, H is enclosure height, D is enclosure depth, measured in
meters.
Difference between air
temperature inside and outside of enclosure is measured in Kelvins (temperature
difference in Kelvins is equal to temperature difference in Celsius).
The difference is found by
deducting the ambient temperature value from the value of temperature inside of
enclosure:
ΔT = Ti - Ta, where
Ti – temperature inside of
enclosure;
Ta – ambient temperature.
If ambient environment temperature
is below zero, for example, Ta = 10°C, whereas the required temperature inside of
enclosure is Ti = +35°C,
then
ΔT = 35 - (-10) = 35 + 10 = 45°K
By putting the formula of
enclosure heat output into general equation the general equation of thermal balance
will be as follows:
Pk = Pv - k · A · ΔT
[Watt]
Positive value of obtained
capacity shows that cooling shall be applied, whereas a negative value shows
that heating shall be used.
Heat exchangers are deployed
for discharge of heat from body to outside atmosphere in the following cases:
if electronic equipment can
operate under a temperature higher that ambient environment temperature;
if humidity level does not
matter;
if the system generates small
or medium amount of heat.
Cooling capacity of heat
exchangers
Selection of a heat exchanger
is similar to that of an air conditioner, in both cases it is necessary to
eliminate internal heat load inside of electronic equipment body. Cooling
capacity of heat exchanger is calculated by dividing the value of actual heat
load by ΔT – difference between maximum temperature of ambient environment
outside the body and maximum allowable operating temperature of electronic
equipment.
Pс = (Qv - Pr) / ΔT,
Pс – efficiency of heat
exchanger;
Qv – heat emission from components
in control enclosure;
Pr [Watt] – heat output
through enclosure body walls (without consideration of insulation ratio);
ΔT – difference between
maximum allowable air temperature inside of enclosure and outside temperature.
The obtained value is the
minimum cooling capacity of heat exchanger. In case no heat exchanger model is
available with a nominal value equal to the obtained value, then a higher
capacity heat exchanger shall be chosen.
You can receive professional
consultation from our engineers.